intermediate work · 700 block of Hague Ave, Hilltop, Columbus OH 43223 (residential)
Run a blower-door infiltration test on a home, the 700 block of Hague Ave, Hilltop
Nobody on the 700 block of Hague Ave, Hilltop has a number for how leaky their home actually is; a calibrated blower-door test turns "it's drafty" into a CFM50 reading and a ranked list of the home's worst air-leak paths for the tightening crew to target. Standard: Ohio Development Services Agency Home Weatherization Assistance Program (HWAP) — the state pass-through of the DOE Weatherization Assistance Program's cold-climate field protocol: blower-door-directed air sealing toward a CFM50 infiltration target, attic insulation to R-49 / wall cavity to R-13, and mandatory pre/post combustion-safety (CO/backdraft) testing before any tightening closes out. Under the LBC Energy petal; SDG 7.3 (energy efficiency) + SDG 13.1 (climate resilience — Columbus winter heating-degree-days). Proof: Photo of the blower-door setup in the entry door frame + CFM50 reading + Photos of each identified top infiltration path + Combustion-safety baseline reading (CO ambient, spillage check) + ranked leak list handed to the occupant Method (Ohio Development Services Agency Home Weatherization Assistance Program (HWAP) — the state pass-through of the DOE Weatherization Assistance Program's cold-climate field protocol: blower-door-directed air sealing toward a CFM50 infiltration target, attic insulation to R-49 / wall cavity to R-13, and mandatory pre/post combustion-safety (CO/backdraft) testing before any tightening closes out. Under the LBC Energy petal; SDG 7.3 (energy efficiency) + SDG 13.1 (climate resilience — Columbus winter heating-degree-days).): 1. Walk the home with the occupant, note combustion appliances present (furnace, water heater, gas range) and photograph each nameplate. 2. Set up the calibrated blower-door fan in the main entry door frame per manufacturer instructions and depressurize the home to the test pressure. 3. Record the CFM50 reading, then walk the home with a smoke pencil/hand to find and photograph the top infiltration paths (rim joist, attic hatch, penetrations, window/door perimeters). 4. Run the baseline combustion-safety check (CO ambient reading, spillage check at draft hoods) with the blower door off before closing out. 5. Deliver the one-page readiness sheet: CFM50 result, ranked leak list, and combustion-safety flag status, and photograph it handed to the occupant. Done when: Photo of the blower-door setup in the entry door frame + CFM50 reading + Photos of each identified top infiltration path + Combustion-safety baseline reading (CO ambient, spillage check) + ranked leak list handed to the occupant
How this work is done
A documented method, so this packet comes out the same whoever does it. Typically 90–240 minutes. Method of record: Ohio Development Services Agency Home Weatherization Assistance Program (HWAP) — the state pass-through of the DOE Weatherization Assistance Program's cold-climate field protocol: blower-door-directed air sealing toward a CFM50 infiltration target, attic insulation to R-49 / wall cavity to R-13, and mandatory pre/post combustion-safety testing before any tightening closes out.
Bring
- calibrated blower-door fan + manometer
- combustion-safety analyzer (CO/ambient + spillage check)
- camera
- caulk gun + spray foam + weatherstripping
- insulation (blown-in or batt, rated to R-49 attic / R-13 wall)
- smoke pencil (leak-path tracing)
- tape measure + infrared thermometer
Steps
- 1. Walk the home with the occupant, note every combustion appliance present, and photograph each nameplate before any work begins.
- 2. Set up the calibrated blower door in the main entry and record the baseline CFM50 reading.
- 3. Trace and photograph the top infiltration paths with a smoke pencil (rim joist, attic hatch, penetrations, window/door perimeters).
- 4. Run the pre-tightening combustion-safety check (ambient CO reading, spillage test at draft hoods) with the blower door off; a failed check stops the job and routes to a licensed HVAC technician before any sealing.
- 5. Air-seal the ranked leak paths in order and bring attic insulation to R-49 / accessible wall cavity to R-13 per the HWAP job sheet, maintaining required soffit-to-ridge ventilation.
- 6. Re-run the blower-door test to confirm the new CFM50 result.
- 7. Run the mandatory post-tightening combustion-safety re-test; a failed re-test stops the job and routes to a licensed HVAC technician for venting correction before further sealing.
- 8. Photograph the finished insulation depth and the passed post-tightening combustion-safety check; enter before/after CFM50, materials used, and the combustion-safety result into the proof record; sign.
If it does not match the plan
- Pre-tightening combustion-safety check fails (elevated CO or spillage) -> STOP: do not tighten the home; route to a licensed HVAC technician before any sealing proceeds.
- Post-tightening combustion-safety re-test fails -> STOP: back off sealing and route to a licensed HVAC technician for venting correction before close-out.
- Home is pre-1978 with disturbed/peeling paint at a sealing surface -> STOP: do not scrape or sand; route to an EPA RRP lead-safe certified pro.
What counts as done
- Before and after CFM50 readings from the same calibrated blower-door setup
- Photos of each sealed leak path and the finished attic/wall insulation depth
- Post-tightening combustion-safety (CO/backdraft) check passed and logged
- Required soffit-to-ridge ventilation maintained after insulation work
Proof is measured against these, not judged by taste.