intermediate work · Swansea Elementary School, 4650 Columbine St, Denver, CO 80216
Swap the classroom HVAC filters, Swansea Elementary (2026-07-17)
Swansea's classrooms sit under the I-70 viaduct in one of Denver's documented air-quality hot spots; a filter that's overdue for a swap is doing less every week to keep that outside air out. Standard: ASHRAE 62.1 ventilation + EPA IAQ baseline (CO2, PM2.5, VOC, RH); LBC Health+Happiness petal. Proof: before/after filter photos + install-date log + GPS Method (ASHRAE 62.1 ventilation + EPA IAQ baseline (CO2, PM2.5, VOC, RH); LBC Health+Happiness petal.): 1. Confirm the filter size and MERV rating on each unit's nameplate and photograph the existing filter as found. 2. Swap each filter for the correct size/rating, noting install date on the frame. 3. Confirm airflow direction arrows are correct on each new filter. 4. Photograph each finished unit and log the swap date for the next cycle. Done when: before/after filter photos + install-date log + GPS
How this work is done
A documented method, so this packet comes out the same whoever does it. Typically 45–90 minutes. Method of record: ASHRAE 62.1 + EPA IAQ / moisture baseline
Bring
- CO2 monitor
- PM2.5 monitor
- temp/RH meter
- moisture meter (mold/moisture scope)
- GPS/address
- camera
Steps
- 1. Confirm the room/unit and address; coordinate to sample during normal occupancy where relevant.
- 2. Photograph the space and any staining/damp/mold.
- 3. Place the monitor in the occupied zone; log CO2 over >=1 occupied hour.
- 4. Record PM2.5, temperature, and relative humidity.
- 5. For moisture/mold scope, take moisture-meter readings at affected vs baseline areas and estimate visible mold area.
- 6. Note ventilation type and any obvious deficiencies.
- 7. Enter the logs, readings, extent notes, photos into the proof record; sign.
If it does not match the plan
- Carbon monoxide > 9 ppm sustained in an occupied space, or any audible CO alarm -> STOP: life-safety hazard. Evacuate, ventilate, and call the gas utility / fire department now. The agent escalates immediately, never sources the leak (NIOSH/ASHRAE CO).
- CO2 sustained > 2000 ppm in an occupied space -> flag acute under-ventilation: recommend increasing outdoor air and reducing occupancy immediately and report to the facility manager (well above the 1000 ppm ASHRAE 62.1 comfort flag).
- CO2 sustained > 1000 ppm -> flag under-ventilation vs ASHRAE 62.1.
- PM2.5 > 35 ug/m3 (24-hr, EPA NAAQS) -> flag elevated particulate; > 55 ug/m3 -> recommend occupants limit exposure / use filtration now.
- Visible mold > 10 sq ft OR active water intrusion -> document only, do not disturb; route to a licensed remediation pro (EPA mold guidance); occupants with respiratory symptoms routed to relocate.
What counts as done
- CO2 logged over >=1 occupied hour
- PM2.5, temperature, and RH recorded
- Moisture readings + visible-mold extent recorded (moisture scope)
- Timestamped photos + address confirm
Proof is measured against these, not judged by taste.