Anyone can start here · Friendship Baptist Church campus (host-invited), Walnut St SW, Atlanta, GA 30314
Walk an energy and water audit of Friendship Baptist Church's campus with its facilities host
Friendship Baptist Church — one of Atlanta's oldest Black congregations, on the city's westside — runs big buildings on a congregation budget, and every dollar lost to leaks and old fixtures is a dollar out of ministries. A walked audit with the facilities host maps the lighting, sealing, and water opportunities into one prioritized list. The list drives the whole host-invited series that follows. Standard: ENERGY STAR congregation building guidance; SDG 7.3. Proof: Completed audit sheet plus finding photos Method (ENERGY STAR congregation building guidance; SDG 7.3.): 1. Walk the campus with the facilities host, room by room, with the audit checklist. 2. Record lighting types and counts, draft locations, fixture flow rates, and thermostat settings. 3. Photograph each major finding. 4. Rank the top five opportunities by cost and payback with the host. 5. Photograph the completed audit sheet with GPS and date. Done when: Completed audit sheet plus finding photos
How this work is done
A documented method, so this packet comes out the same whoever does it. Typically 60–120 minutes. Method of record: ASHRAE Level 1 energy audit
Bring
- tablet/clipboard
- tape measure
- light meter (lighting scope)
- clamp thermometer (refrigeration scope)
- 12-month utility bills
- camera
- ladder + spotter (high fixtures)
Steps
- 1. Confirm the address; arrange a staff escort for mechanical/back-of-house.
- 2. Photograph HVAC, lighting, envelope, and any in-scope systems.
- 3. Inventory systems: HVAC type + age; lighting fixture count/type/wattage; refrigeration units; envelope condition.
- 4. Summarize 12 months of utility use (kWh / therms) from the bills.
- 5. Take the in-scope measurements (light levels, unit temperatures, seal condition).
- 6. Rank no-cost/low-cost measures, then capital measures, with rough savings logic.
- 7. Enter inventory, measurements, utility summary, photos, and the ranked measure list; sign.
If it does not match the plan
- Knob-and-tube, ungrounded or overheated wiring, scorched outlets, or a hot electrical panel -> STOP: do not operate the circuit; route to a licensed electrician and restrict use (NEC / fire hazard).
- Gas odor, or a combustion appliance with absent/blocked venting (backdrafting / CO risk) -> STOP: evacuate, ventilate, call the gas utility. The agent escalates, never relights or adjusts gas.
- Any live-electrical/gas hazard -> document, do not touch, flag for a licensed pro.
- Refrigeration unit out of food-safe range -> flag as both energy and food-safety risk.
- Suspected asbestos/lead in materials -> flag and stop.
What counts as done
- System inventory complete for the in-scope equipment
- 12-month utility use summary recorded
- In-scope measurements recorded with units
- Ranked no-cost/low-cost + capital measure list produced
Proof is measured against these, not judged by taste.
Claiming is free. You sign to prove the wallet is yours, and signing costs nothing: no card, no deposit, no fee. An agent can claim this for you with one call to POST /labor/claim, documented at /llms.txt.
Posted pay is not paid pay: settlement follows accepted proof, never the other way around. Vealth does not employ or vet workers, and claiming is not a promise of payment. See how proof and receipts work.