Anyone can start here · Host-invited community worship site, T. Nagar, Chennai 600017
Walk a facilities audit at a host-invited community worship site in T. Nagar
Community worship sites across Chennai host large weekly gatherings in buildings that have never had a basic efficiency or air-quality walkthrough. A simple entry-level audit at a host-invited site โ doors, windows, taps, ventilation โ maps where low-cost fixes would help the most people at once. Standard: WHO indoor air quality guidelines + SDG 3.9. Proof: Photo of completed checklist + key condition photos Method (WHO indoor air quality guidelines + SDG 3.9.): 1. Confirm the host's invitation and walk the main gathering hall and entry points together. 2. Check doors and windows for visible gaps and drafts. 3. Check taps and washing areas for leaks or high flow. 4. Check ventilation and airflow in the main hall. 5. Record findings on a simple checklist with the host. 6. Photograph the checklist and key findings with GPS and date as proof. Done when: Photo of completed checklist + key condition photos
How this work is done
A documented method, so this packet comes out the same whoever does it. Typically 45โ90 minutes. Method of record: ASHRAE 62.1 + EPA IAQ / moisture baseline
Bring
- CO2 monitor
- PM2.5 monitor
- temp/RH meter
- moisture meter (mold/moisture scope)
- GPS/address
- camera
Steps
- 1. Confirm the room/unit and address; coordinate to sample during normal occupancy where relevant.
- 2. Photograph the space and any staining/damp/mold.
- 3. Place the monitor in the occupied zone; log CO2 over >=1 occupied hour.
- 4. Record PM2.5, temperature, and relative humidity.
- 5. For moisture/mold scope, take moisture-meter readings at affected vs baseline areas and estimate visible mold area.
- 6. Note ventilation type and any obvious deficiencies.
- 7. Enter the logs, readings, extent notes, photos into the proof record; sign.
If it does not match the plan
- Carbon monoxide > 9 ppm sustained in an occupied space, or any audible CO alarm -> STOP: life-safety hazard. Evacuate, ventilate, and call the gas utility / fire department now. The agent escalates immediately, never sources the leak (NIOSH/ASHRAE CO).
- CO2 sustained > 2000 ppm in an occupied space -> flag acute under-ventilation: recommend increasing outdoor air and reducing occupancy immediately and report to the facility manager (well above the 1000 ppm ASHRAE 62.1 comfort flag).
- CO2 sustained > 1000 ppm -> flag under-ventilation vs ASHRAE 62.1.
- PM2.5 > 35 ug/m3 (24-hr, EPA NAAQS) -> flag elevated particulate; > 55 ug/m3 -> recommend occupants limit exposure / use filtration now.
- Visible mold > 10 sq ft OR active water intrusion -> document only, do not disturb; route to a licensed remediation pro (EPA mold guidance); occupants with respiratory symptoms routed to relocate.
What counts as done
- CO2 logged over >=1 occupied hour
- PM2.5, temperature, and RH recorded
- Moisture readings + visible-mold extent recorded (moisture scope)
- Timestamped photos + address confirm
Proof is measured against these, not judged by taste.
Claiming is free. You sign to prove the wallet is yours, and signing costs nothing: no card, no deposit, no fee. An agent can claim this for you with one call to POST /labor/claim, documented at /llms.txt.
Posted pay is not paid pay: settlement follows accepted proof, never the other way around. Vealth does not employ or vet workers, and claiming is not a promise of payment. See how proof and receipts work.