Run a blower-door-directed retrofit on the Kelley Street triple-decker in Manchester (2026-07-20)

With basic sealing and attic insulation already done at this Kelley Street triple-decker, the building needs a diagnostic-directed pass to catch the remaining leakage points a simple walk-through would miss. This is the advanced rung of the weatherization craft series, capping the work already invested at this address. Standard: Efficiency Maine / NEEP cold-climate weatherization guidance Proof: Before and after blower door test numbers plus photos of the sealed points and a GPS tag. Method (Efficiency Maine / NEEP cold-climate weatherization guidance): 1. Set up the blower door and run a baseline depressurization test. 2. Walk the home with the door running and mark every point where air rushes in. 3. Seal each marked point with the appropriate material, caulk, foam, or gasket. 4. Re-run the blower door test to confirm the leakage reduction. 5. Log the before and after test numbers as proof of the retrofit. Done when: Before and after blower door test numbers plus photos of the sealed points and a GPS tag.

Where
58 Kelley St, Manchester, NH 03102
Pay
$560 proposed

This packet is not funded yet, so this figure is a proposed price and not money waiting in escrow. If a buyer funds it, approved proof settles that price onchain. If nobody funds it, approved proof earns provable credit toward the work instead of cash. You see which before you claim, never after.

Proof
Before and after blower door test numbers plus photos of the sealed points and a GPS tag.

This is exactly what gets it approved. Nothing settles without it.

Level
advanced
Open until
2026-08-19

How this work is done

A documented method, so this packet comes out the same whoever does it. Typically 90–240 minutes. Method of record: Ohio Development Services Agency Home Weatherization Assistance Program (HWAP) — the state pass-through of the DOE Weatherization Assistance Program's cold-climate field protocol: blower-door-directed air sealing toward a CFM50 infiltration target, attic insulation to R-49 / wall cavity to R-13, and mandatory pre/post combustion-safety testing before any tightening closes out.

Bring

Steps

  1. 1. Walk the home with the occupant, note every combustion appliance present, and photograph each nameplate before any work begins.
  2. 2. Set up the calibrated blower door in the main entry and record the baseline CFM50 reading.
  3. 3. Trace and photograph the top infiltration paths with a smoke pencil (rim joist, attic hatch, penetrations, window/door perimeters).
  4. 4. Run the pre-tightening combustion-safety check (ambient CO reading, spillage test at draft hoods) with the blower door off; a failed check stops the job and routes to a licensed HVAC technician before any sealing.
  5. 5. Air-seal the ranked leak paths in order and bring attic insulation to R-49 / accessible wall cavity to R-13 per the HWAP job sheet, maintaining required soffit-to-ridge ventilation.
  6. 6. Re-run the blower-door test to confirm the new CFM50 result.
  7. 7. Run the mandatory post-tightening combustion-safety re-test; a failed re-test stops the job and routes to a licensed HVAC technician for venting correction before further sealing.
  8. 8. Photograph the finished insulation depth and the passed post-tightening combustion-safety check; enter before/after CFM50, materials used, and the combustion-safety result into the proof record; sign.