Repair the curb ramp at Broad Street and Dexter Street in Central Falls (2026-07-20)
The curb ramp at Broad Street and Dexter Street in Central Falls has a cracked surface and a missing detectable warning strip, a hazard on one of the city's busiest walking corridors. The city wants it repaired. Standard: ADA/PROWAG public right-of-way safety standard Proof: Before and after photos of the repaired ramp plus a GPS tag. Method (ADA/PROWAG public right-of-way safety standard): 1. Inspect the ramp surface for cracks, spalling, or a broken detectable warning strip. 2. Clear debris and grind down any trip hazard at the ramp edge. 3. Patch cracked or spalled concrete with a matching repair compound. 4. Reset or replace the detectable warning strip if damaged. 5. Photograph the repaired ramp and confirm the slope is walkable. Done when: Before and after photos of the repaired ramp plus a GPS tag.
How this work is done
A documented method, so this packet comes out the same whoever does it. Typically 240–600 minutes. Method of record: Curb ramp repair/retrofit to ADA + PROWAG R304 (slope, landing, detectable warning surface), under municipal right-of-way permit — trained crew with wet-cut dust controls; assess→repair→verify
Bring
- right-of-way permit + cones/barricades + pedestrian detour signage
- smart level / digital inclinometer + tape measure
- concrete tools + detectable warning surface (truncated dome) panel per city standard
- wet-cut saw with water feed (dust control)
Steps
- 1. ASSESS: measure the existing ramp against PROWAG R304 (running slope ≤8.3%, cross-slope ≤2%, landing, flush transition, detectable warning) and photograph each failure; confirm permit + utility locates before cutting.
- 2. Set up cones/barricades and a safe pedestrian detour outside the work zone.
- 3. Remove the failed ramp section with wet-cut dust controls; form and place the corrected ramp geometry per the city standard drawing.
- 4. Set the detectable warning surface (truncated domes) aligned and embedded per spec; finish transitions flush with the gutter.
- 5. VERIFY: re-measure every R304 dimension with the smart level, photograph readings + before/after from matching vantage, water-test the gutter flow line, and close out the permit.
If it does not match the plan
- No permit or no utility locate -> STOP: do not cut.
- Cutting without water-fed dust control -> STOP (respirable silica).
- Geometry cannot meet R304 within the existing footprint -> document and route to the city's ADA transition-plan engineer instead of pouring a non-compliant ramp.
What counts as done
- Measured running slope ≤8.3% and cross-slope ≤2% with level photos
- Detectable warning surface installed per standard (alignment + embed photos)
- Flush gutter transition verified (no lip >1/4 inch; water flows along the gutter line)
- Before/after photos + permit close-out reference
Proof is measured against these, not judged by taste.