advanced work · Succ Energywalk
Follow the building-energy audit with a heat-pump swap, Hillside Public Library, Reno NV.
Fund it for $220. Proof lands onchain when it's done.
$220 proposed
This packet is not funded yet, so this figure is a proposed price and not money waiting in escrow. If a buyer funds it, approved proof settles that price onchain. If nobody funds it, approved proof earns provable credit toward the work instead of cash — recorded, and readable any time at vealth.net/labor/credit/(your wallet). You see which before you claim, never after.
Open, but not claimable yet. restricted: permit-required, regulated — Regulated or permit-required work cannot be claimed on this rail yet. It stays readable; voting and pledging are free, and funding is separate from claiming.
What the work involvesThe energy audit at Hillside Public Library, Reno NV found an aging, inefficient heating/cooling system with no low-carbon path scoped. Swap the old unit for a heat pump now: sized, permitted, and commissioned.
How this work is done
A documented method, so this packet comes out the same whoever does it.
Bring
- Manual J/S load calculation + approved permit
- heat-pump equipment (outdoor + indoor units), line set, pad/brackets, condensate handling
- refrigerant gauges/scale + vacuum pump + torque tools (EPA 608-certified technician)
- multimeter + thermometer/anemometer for commissioning airflow and delta-T
Steps
- 1. ASSESS: verify the Manual J/S sizing against the home (envelope, ductwork or head locations), confirm electrical capacity for the new circuit, and photograph the existing system and nameplates.
- 2. Decommission and recover refrigerant from the old system per EPA 608; remove equipment for lawful disposal/recycling and document it.
- 3. Set and mount the new equipment, run and braze/flare the line set, pull vacuum to spec, and release/weigh in charge per manufacturer; a licensed electrician lands the new circuit and disconnect.
- 4. Commission: verify airflow, refrigerant charge (subcooling/superheat per spec), heating and cooling delta-T, and condensate drainage; set up controls/thermostat.
- 5. VERIFY: pass the mechanical/electrical inspection; record commissioning numbers and before/after photos; leave the owner the manual, warranty registration, and maintenance schedule.
What counts as done
- Old-unit nameplate photo + EPA 608 refrigerant-recovery record
- Commissioning sheet (charge, airflow, both-mode delta-T)
- Permit inspection pass reference
- Before/after photos
Proof is measured against these, not judged by taste.
What is promised, and what is not.
Three separate acts, never one: a vote is a free signed preference that moves no money; a pledge is free signed backing intent, balance-checked, that moves no money and never marks the packet funded; funding is a real payment that backs the wage. Funding starts at one cent, an omitted amount pays what the packet still needs, and only an explicit amount above the remaining is recorded as a premium for the worker. Money settles only on accepted proof. An agent can fund it in one x402 call: POST /nurture/fund {"workId":"WORK_1788201597858_cli9140","funderWallet":"0xYOU"}.
An agent can claim this for you with one call to POST /labor/claim, documented at /llms.txt.
Every stage this packet actually passes, claim to settlement, is public in its receipt trail. A stage that has not happened is not claimed.
Posted pay is not paid pay: settlement follows accepted proof, never the other way around. Vealth does not employ or vet workers, and claiming is not a promise of payment. See how proof and receipts work.